Preliminary ABAQUS Studies
Last updated Friday, April 11, 1997, at 1:06 PM
Copyright © 1996, 1997
Kirk Martini
Comparison with Experiment
The Yokel Studies
In the early 1970s, the National Bureau of Standards (now the National Institute of Science and Technology, NIST) conducted a series of tests on a variety of unreinforced masonry construction types using panels subjected to a static vertical compression load, followed by a gradually increasing lateral pressure exerted by an inflated air bag. The figure below shows the testing configuration for the 4-foot by 8-foot test panels.
|
The testing configuration for the Yokel Studies Yokel 1971, figure 5.1,
p. 8] |
The tests include solid and hollow brick and concrete block, plus composite construction. For each type of construction, tests were conducted for a range of vertical compression loads. The presentation below focuses on solid block and brick construction with light compressive loads, comparing results of the block-interface model with Yokel's published experimental results.
A Statically Loaded Solid Block Wall
One of the Yokel tests included a panel composed of solid 8-inch concrete blocks with a 25 Kip vertical surcharge. The light load and solid masonry construction are similar to conditions at ancient masonry construction, and were selected for verification.
The figure below shows a deformed finite element model of the test panel. The vertical support at the bottom of the wall is modelled with springs to model the flexibility of the 0.5 in fiberboard. The interface elements at the base of the wall have a low coefficient of friction to account for sliding of the fiberboard. The horizontal loading bars are modelled as displacement boundary conditions. The vertical loading is modelled as concentrated forces on each node at the top of the wall so that the forces maintain the vertical direction even when the top of the wall rotates. The lateral pressure is modelled as a distributed load on the element faces.
|
The deformed shape at failure predicted by the block-interface model for test 3-3 of Yokel 1971]. The red triangles indicate displacement boundary conditions, and the white spirals at the bottom of the wall indicate spring elements used to model the flexibility of the 0.5 fiberboard underlying the wall
assembly. Displacement magnification factor = 10.
|
|
A detail of the image from above, showing the pattern of cracking in
the analytic model. Note the small cracks forming above and below the
primary crack. Displacement magnification factor = 10.
|
The image below shows the similarity of the failure pattern in the analytic
model and the test specimen. Note that the photograph shows a test specimen with a
much higher vertical compression force (150 Kips), so that there the wall in
the photo shows compression failure where the blocks have spalled on the face
opposite the camera.
|
A photograph of a solid block wall at failure. This wall was subjected to a much larger vertical
compression load (150 Kips) than that of the model above (25 kips), and so shows signs of compression failure, but the pattern of tension cracking at one bed joint is similar in the analytic
model and the experiment.
Yokel 1971, p. 19, figure 6.13, test 3-6]
|
Several variations of the finite element model were explored in comparison
with the experimental results. The key variables were the following:
- The number of laminations: The mesh subdivided the wall into a series
of vertical layers called laminations. The model shown above includes 6 laminations.
The study examined models with 4, 6, and 8 laminations.
- The number of element layers per course: The mesh also subdivides the wall into
horizontal layers called courses. A course is bounded by interface elements top and
bottom, and corresponds to a row of blocks in the actual wall. Courses may be further subdivided
into horizontal groups called element layers, where there are no horizontal interface
elements between the solid elements. The study examined models with 1, 3 and 5 element layers
per course.
The figure below illustrates the organization of laminations, courses and
element layers, using the deformed shape of a model with six laminations, and
two element layers per course.
|
A model using six laminations (the vertical layers) and two element layers per course, where
a course is a horizontal group between interface elements. Magnification factor = 50.
|
The figure below compares the load-displacement characteristics of various models with
Yokel's experimental results. The curves reveal the following trends.
- The model with 4 laminations severely overestimates the elastic stiffness
and underestimates the displacement capacity.
- The model with 6 laminations and 1 element layer per course is better than the 4-lamination
model, but still tends to overestimate elastic stiffness. An 8-lamination model (not shown on the
figure) has a load-displacement curve nearly identical to that of the 6-lamination model.
- The model with 6 laminations and 3 element layers per course does a much better job in the
elastic range. It is clear that the 1-layer model overestimates the flexural stiffness of
the courses. In the inelastic range, however, the 1-layer and 3-layer models
take the same path at a displacement of approximate 0.18 inches, indicating that
the behavior in this range is dominated by cracking rather than block flexure.
- The model with five element layers per course is close to the curve for the
3-layer model, but its displacement at maximum load is 0.38 in, rather than 0.18 in
for the 3-layer model. This is much closer to the experimental result.
- Although the five layer model estimates the displacement capacity much better than
the other models, all of the models predict the maximum load capacity within about 5 percent.
|
Load-displacement curves comparing the experimental and analytic results. The analytic model
overestimates the stiffness and underestimates the strength and displacement capacity, although
the general pattern is similar. (Experimental curve is derived from data in figure 8.19 p. 44, and
table 6.2, p. 10
Yokel 1971]
|
A Statically Loaded Solid Brick Wall
Yokel included another test that involved a solid brick wall that failed by
instability and cracking rather than compression crushing. This test, designated
6-3, was type S brick with high-bond mortar and a 140 Kip vertical surcharge.
The images below show an overall view of the analytic model and a photograph of
one of the test specimens.
|
The deformed shape at failure predicted by the block-interface model for test
6-3 of Yokel [1971]. The white spirals at the bottom of the wall indicate spring
elements used to model the flexibility of the 0.5 fiberboard underlying the wall
assembly. Displacement magnification factor = 10.
|
|
A photograph from Yokel [1976], with the caption: "Typical failure of brick walls with
low vertical compressive loads." (fig. 6.14, p. 20)
|
Two variations of this model were developed, one with 4 laminations and 1 element layer per course,
and another with 4 laminations and 2 element layers per course. The figure below compares the
published load-displacement curve from the experiment with those of the analytic models.
|
Load-displacement curves comparing the experimental and analytic results. The analytic model
overestimates the stiffness and strength, but underestimates displacement capacity. (Experimental curve derived from
figure 8.21, p. 47 and table 6.4. p. 11
[Yokel 1971]
|
The figure reveals the following points:
- As with the concrete block comparison, the analytic models tend to overestimate
stiffness in the elastic range, and underestimate the displacement at maximum
strength. Using more element layers per course gives better agreement in the elastic range.
- Unlike the concrete block models, there is a notable difference in
strength between analytic models: The 2-layer model is clearly weaker, and much closer to
the experimental results, than the one-layer model.
Last updated Friday, April 11, 1997, at 1:06 PM
Copyright © 1996, 1997
Kirk Martini
Please send comments or questions to
Martini@virginia.edu
Table of Contents